SERIES: Metering Room at Ground Level - Covered Open Space
PLANS:
AUTOCAD FILE (dwg file) - Metering Room at Ground level - Covered Open Space.dwg
Autodesk Design Web Format File (dwg file) -Metering Room at Ground level - Covered Open Space.dwf
| DWG NO. |
TYPE-LAYOUT |
CAPACITY IN NUMBER OF METERS |
TOTAL LOAD CAPACITY |
PROVISION FOR PHOTOVOLTAIC CELLS |
MAIN USE |
| TQ/256-1 |
EAC and Electrician's Areas Side by Side |
<48 Equivelant 1-phase |
> 300KVA |
POSSIBLE |
Block of Flats / Comm Development |
| TQ/256-2 |
EAC and Electrician's Areas Side by Side |
<48 Equivelant 1-phase |
> 300KVA |
POSSIBLE |
Block of Flats / Comm Development |
| TQ/256-3 |
EAC and Electrician's Areas Side by Side |
>48 Equivelant 1-phase |
> 300KVA |
POSSIBLE |
Block of Flats / Comm Development |
| TQ/256-4 |
EAC and Electrician's Areas Side by Side |
>48 Equivelant 1-phase |
> 300KVA |
POSSIBLE |
Block of Flats / Comm Development |
| TQ/256-5 |
EAC and Electrician's Areas Opposite each other |
>48 Equivelant 1-phase |
> 300KVA |
POSSIBLE |
Block of Flats / Comm Development |
| TQ/256-6 |
EAC and Electrician's Areas Opposite each other |
>48 Equivelant 1-phase |
> 300KVA |
POSSIBLE |
Block of Flats / Comm Development |
| TQ/256-7 |
EAC and Electrician's Areas Opposite each other |
>48 Equivelant 1-phase |
> 300KVA |
POSSIBLE |
Block of Flats / Comm Development |
| TQ/256-8 |
Cabinet Type |
<48 Equivelant 1-phase |
> 300KVA |
POSSIBLE |
Block of Flats / Comm Development |
| TQ/256-9 |
Cabinet Type |
>48 Equivelant 1-phase |
> 300KVA |
POSSIBLE |
Block of Flats / Comm Development |
| TQ/256-10 |
Typical plan for load>300KVA |
>48 Equivelant 1-phase |
> 300KVA<600KVA |
POSSIBLE |
Block of Flats / Comm Development |
COMMENTS
-
ONE THREE PHASE METER OCCUPIES TWO EQUIVELANT METER POSITIONS (SINGLE PHASE)
-
ONE METERING PANEL (ELECTRIC LOAD>100A) OCCUPIES SPACE OF 80CM WIDTH AND 120CM HEIGHT
-
ON THE METER BOARD A SPACE MUST BE PROVIDED FOR 2-3 EQUIVELANT METER POSITIONS FOR EAC (TARIFF RECEIVERS)
-
FOR STORAGE RADIATORS A 3 PHASE METER IS REQUIRED (TWO EQUIVELANT SINGLE PHASE) + 1 POSITION FOR RECEIVER
- FOR ELECTRICAL LOADS > 300KVA MODIFICATIONS TO THE TYPICAL PLANS REQUIRED - COMMUNICATION WITH EAC